
- Violating or ignoring code restrictions,
- Not installing D/W/V with at least a 1/4"
slope per one foot pipe,
- Not properly venting or trapping all fixtures,
- Attaching too many fixtures to a drain or vent
pipe,
- Using pipes that are too small,
- Not providing enough cleanouts or not providing
cleanouts at the prescribed places,
- Venting the fixture too far from the fixture's
trap,
- Not properly aligning tubing into fittings or
stop valves. (Forcing the nut onto the compression ring at an angle
when the tubing is at an angle will cause a leak.)
- Using a fitting in a wrong position,
- Installing rough plumbing in the wrong
location,
- Reducing pipe size as the pipes run downstream,
- Cutting pipe too long and not allowing for the
ridge in the fittings, and
- Forcing the trap and waste arm fittings out of
alignment and putting too much stress on the nuts and washers in the
tubing.
- Make certain the compression tubing is put in
the fittings so that it is evenly tightened.
|